OPUS INV OC0864 Wall Cabinet Inverter System

OPUS Inverter Systems are robust, free convection cooled, N+1 redundant DC to AC power conversion solutions for critical infrastructure applications. Inverter systems can be integrated to OPUS Power System and monitored via VIDI controller. This 6kVA Cabinet system includes slots for 5 x inverter modules, static bypass aand manual bypass. Load distribution can be configured according to the request.

Key features

  • Modular 1kVA-6kVA wall-mount AC power system
  • N+1 redundancy, on-line / off-line supply modes
  • Natural convection cooling or fan versions
  • Full integration to OPUS DC power systems
  • Nominal Input voltages
    24VDC, 48-60VDC, 110-125VDC, 220 VDC
  • Bypass mains input & AC output 200-240VAC 50/60Hz
  • Battery connection: 1-3 MCB or Switch Fuse
  • Configurable load distribution
  • EMC ratings:
    Cabinet: EN61439-1, EN61439-2
    Inverters: EN 61000-6-1 / -2 / -3 / -4
  • Safety ratings:
    Cabinet: EN61439-1, EN61439-2
    Inverters: EN 62368-1

Applications

  • Critical infrastructure
  • Transmission substations
  • Distribution substations
  • Railway signaling and substations
  • Process industries
  • Telecommunications
Model number
Power Level (VA)
Module Positions
Input Voltage (VDC)
Input Voltage (VAC)
V1 Out Nom (V)
Cooling
OPUS INV 24-6.0 OC0864 F
Power Level (VA) 6000
Module Positions 5
Input Voltage (VDC) 20 - 32
Input Voltage (VAC) 200 - 240
V1 Out Nom (V) 200 - 240
Cooling Natural Convection or Fan
Control & Monitoring
OPUS VIDI Controller, relays, RS-232, SNMP
Operating temperature range
-10°C to +60°C, see derating
IP Rating
IP20 / IP21
Safety
EN61439-1 / EN61439-2
OPUS INV 48/60-6.0 OC0864 F
Power Level (VA) 6000
Module Positions 5
Input Voltage (VDC) 40 - 72
Input Voltage (VAC) 200 - 240
V1 Out Nom (V) 200 - 240
Cooling Natural Convection or Fan
Control & Monitoring
OPUS VIDI Controller, relays, RS-232, SNMP
Operating temperature range
-10°C to +60°C, see derating
IP Rating
IP20 / IP21
Safety
EN61439-1 / EN61439-2
OPUS INV 110/125-6.0 OC0864 F
Power Level (VA) 6000
Module Positions 5
Input Voltage (VDC) 88 - 150
Input Voltage (VAC) 200 - 240
V1 Out Nom (V) 200 - 240
Cooling Natural Convection or Fan
Control & Monitoring
OPUS VIDI Controller, relays, RS-232, SNMP
Operating temperature range
-10°C to +60°C, see derating
IP Rating
IP20 / IP21
Safety
EN61439-1 / EN61439-2
OPUS INV 220-6.0 OC0864 F
Power Level (VA) 6000
Module Positions 5
Input Voltage (VDC) 178 - 275
Input Voltage (VAC) 200 - 240
V1 Out Nom (V) 200 - 240
Cooling Natural Convection or Fan
Control & Monitoring
OPUS VIDI Controller, relays, RS-232, SNMP
Operating temperature range
-10°C to +60°C, see derating
IP Rating
IP20 / IP21
Safety
EN61439-1 / EN61439-2

OPUS INV Wall mountable power systems are an industrial grade solution family that converts battery secured DC power to uninterrupted AC power. All typical battery systems from nominal 24V to 220VDC are supported. With highly efficient, convection-cooled inverters and a highly modular mechanical structure, the OPUS INV Series can be easily configured to meet a multitude of utility, industrial and rail applications.

OPUS INV Wall mount systems come in an IP20 / IP21 enclosure and consist of the EIM inverters  up to 5 modules, 6kVA static bypass and manual bypass and MCB protection for the mains and DC inputs. For load connections there are both bulk screw terminal outputs and configurable MCBs.