Skip to content

OPUS C 7U DC Power Systems

OPUS C 7U 19″ rack power systems are robust, N+1 redundant, free convection cooled backup power solutions for critical infrastructure applications such as distribution and transmission substations, process control industries and telecommunications.

Key features

  • Convection cooling
  • Max 4.8 kW output power (3.3 kW for 24 VDC models)
  • N+1 Redundancy
  • Models include 24, 48, 60, 110, 125 & 220 VDC standard output variants
  • Battery connection: 1 string with full current, MCB protection
  • Options: Battery LVD, Temperature sensor, wall mounting & IP21 kit
  • Safety: IEC/EN 60950-1

Applications

  • Critical infrastructure
  • Transmission substations
  • Distribution substations
  • Process industries
  • Telecommunications
Model number
Power Out Max (kW)
Input Voltage (VAC)
Output Voltage Range (VDC)
Output Current Max (A)
Cooling
OPUS C 24 3.3 R 7U F
Power Out Max (kW) 3.3
Input Voltage (VAC) 180 - 275
Output Voltage Range (VDC) 21 - 31
Output Current Max (A) 229
Cooling Convection
Max # Outputs
1
Module Positions
3
V1 Out Min (V)
21
V1 Out Nom (V)
24
V1 Out Max (V)
31
Efficiency Rating (%)
90
Operating Altitude (m)
2000
Operating temperature range
-5 to 45°C
IP Rating
IP20
Safety
IEC/EN 60950-1
OPUS C 48 4.8 R 7U F
Power Out Max (kW) 4.8
Input Voltage (VAC) 180 - 275
Output Voltage Range (VDC) 42 - 58
Output Current Max (A) 164
Cooling Convection
Max # Outputs
1
Module Positions
3
V1 Out Min (V)
42
V1 Out Nom (V)
48
V1 Out Max (V)
58
Efficiency Rating (%)
92
Operating Altitude (m)
2000
Operating temperature range
-5 to 45°C
IP Rating
IP20
Safety
IEC/EN 60950-1
OPUS C 60 4.8 R 7U F
Power Out Max (kW) 4.8
Input Voltage (VAC) 180 - 275
Output Voltage Range (VDC) 51 - 72
Output Current Max (A) 134
Cooling Convection
Max # Outputs
1
Module Positions
3
V1 Out Min (V)
51
V1 Out Nom (V)
60
V1 Out Max (V)
72
Efficiency Rating (%)
91
Operating Altitude (m)
2000
Operating temperature range
-5 to 45°C
IP Rating
IP20
Safety
IEC/EN 60950-1
OPUS C 110 4.8 R 7U F
Power Out Max (kW) 4.8
Input Voltage (VAC) 180 - 275
Output Voltage Range (VDC) 97 - 132
Output Current Max (A) 72
Cooling Convection
Max # Outputs
1
Module Positions
3
V1 Out Min (V)
97
V1 Out Nom (V)
110
V1 Out Max (V)
132
Efficiency Rating (%)
Operating Altitude (m)
2000
Operating temperature range
-5 to 45°C
IP Rating
IP20
Safety
IEC/EN 60950-1
OPUS C 220 4.8 R 7U F
Power Out Max (kW) 4.8
Input Voltage (VAC) 180 - 275
Output Voltage Range (VDC) 189 - 265
Output Current Max (A) 36
Cooling Convection
Max # Outputs
1
Module Positions
3
V1 Out Min (V)
189
V1 Out Nom (V)
220
V1 Out Max (V)
265
Efficiency Rating (%)
91
Operating Altitude (m)
2000
Operating temperature range
-5 to 45°C
IP Rating
IP20
Safety
IEC/EN 60950-1

The OPUS C 7U 19″ rack-mount power system are configured to customer specifications utilizing OPUS C standard building blocks consisting of the MRC series rectifiers, VIDI+ controllers, mains and battery connections, and a wide selection of load distribution options. OPUS C systems are available in  24, 48, 60, 110, 125 and 220 VDC standard output variants and have a max output power of 4.8 kW (3.3 kW for 24 VDC models).

System options include a battery LVD, temperature sensor, wall-mount kit and IP21 cover kit.

The systems meet IEC 60950-1 safety standards and the following EMC standards: Emissions: IEC/EN 61000-6-4, Immunity: IEC/EN 61000-6-2, Harmonics: IEC/EN 61000-3-2, and Voltage Fluctuations & Flicker: IEC/EN 61000-3-3.

OPUS Battery Fuse Box
• Wall Mountable Fuse Box for Battery Installations
• Switch Fuse Protection
• Configurable Fuse Link
• Up to 125A

Datasheet – OPUS Battery Fuse Box

OPUS Battery Cabinet For Front Terminal Batteries
• 4 Battery shelves 320 x 530 x 595 mm
• User terminals 35 mm (8 pcs)
• Cable entry from top, neoprene cable glands (optional bottom cable entry)
• Adjustable legs

Datasheet – OPUS Battery Cabinet For Front Terminal Batteries

OPUS IC Battery Cabinets with Switch Fuse Protection
• Battery shelves for up to 4 x 48V/190Ah batteries
• Switch fuse protected battery strings (4 x 125A NH00 – fuse monitoring)
• Cable entry from top
• Ventilation output on the top
• Adjustable legs
• Strong welded structure
• Top lifting eyes

Datasheet – OPUS IC Battery Cabinets with Switch Fuse Protection