OPUS C 7U DC Power Systems
OPUS C 7U 19″ rack power systems are robust, N+1 redundant, free convection cooled backup power solutions for critical infrastructure applications such as distribution and transmission substations, process control industries and telecommunications.
Key features
- Convection cooling
- Max 4.8 kW output power (3.3 kW for 24 VDC models)
- N+1 Redundancy
- Models include 24, 48, 60, 110, 125 & 220 VDC standard output variants
- Battery connection: 1 string with full current, MCB protection
- Options: Battery LVD, Temperature sensor, wall mounting & IP21 kit
- Safety: IEC/EN 60950-1
Applications
- Critical infrastructure
- Transmission substations
- Distribution substations
- Process industries
- Telecommunications
The OPUS C 7U 19″ rack-mount power system are configured to customer specifications utilizing OPUS C standard building blocks consisting of the MRC series rectifiers, VIDI+ controllers, mains and battery connections, and a wide selection of load distribution options. OPUS C systems are available in 24, 48, 60, 110, 125 and 220 VDC standard output variants and have a max output power of 4.8 kW (3.3 kW for 24 VDC models).
System options include a battery LVD, temperature sensor, wall-mount kit and IP21 cover kit.
The systems meet IEC 60950-1 safety standards and the following EMC standards: Emissions: IEC/EN 61000-6-4, Immunity: IEC/EN 61000-6-2, Harmonics: IEC/EN 61000-3-2, and Voltage Fluctuations & Flicker: IEC/EN 61000-3-3.
OPUS Battery Fuse Box
• Wall Mountable Fuse Box for Battery Installations
• Switch Fuse Protection
• Configurable Fuse Link
• Up to 125A
OPUS Battery Cabinet For Front Terminal Batteries
• 4 Battery shelves 320 x 530 x 595 mm
• User terminals 35 mm (8 pcs)
• Cable entry from top, neoprene cable glands (optional bottom cable entry)
• Adjustable legs
Datasheet – OPUS Battery Cabinet For Front Terminal Batteries
OPUS IC Battery Cabinets with Switch Fuse Protection
• Battery shelves for up to 4 x 48V/190Ah batteries
• Switch fuse protected battery strings (4 x 125A NH00 – fuse monitoring)
• Cable entry from top
• Ventilation output on the top
• Adjustable legs
• Strong welded structure
• Top lifting eyes
Datasheet – OPUS IC Battery Cabinets with Switch Fuse Protection