Skip to content

OPUS HE 12U DC Power Systems

OPUS HE power systems offer a robust, free air convection cooled, N+1 redundant backup power solution for critical infrastructure applications such as transmission and distribution substations, process industries, railway signaling and substations, and telecommunications.

Configurator of the OPUS HE 19″ 12U Rack Power System

Key features

  • Efficiency up to 97%
  • Natural convection cooled – fan free
  • Standard output voltages: 24, 48, 60, 110, 125 and 220 VDC
  • Max 10 kW output power, 7.5 kW for 24 VDC models
  • N+1 redundancy
  • Optional load distribution modules are 2-pole or 1-pole MCB
  • Battery connection: 1 string with full current
  • Options: Battery LVD, temperature sensor, wall mounting & IP21 cover kit
  • EMC ratings:
    Rack: EN61439-1, EN61439-2
    Rectifiers: EN 61000-6-1 / -2 / -3 / -4 / -5
    EN50121-4 Rail, ETSI EN 300386 (48/60V)
  • Safety ratings:
    Rack: EN61439-1, EN61439-2
    Rectifiers: EN 62368-1, EN 50124-1 rail

Applications

  • Critical infrastructure
  • Power transmission substations
  • Power distribution substations
  • Railway signaling and substations
  • Process industries
  • Telecommunications
Model number
Power Out Max (kW)
Input Voltage (VAC)
Output Voltage Range (VDC)
Output Current Max (A)
Cooling
OPUS HE 24-7.5 R12U F
Power Out Max (kW) 7.5
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 21 - 33
Output Current Max (A) 312.5
Cooling Natural Convection
Max # Outputs
1
Module Positions
5
V1 Out Min (V)
21
V1 Out Nom (V)
24
V1 Out Max (V)
33
Efficiency Rating (%)
97
Operating Altitude (m)
2000
Operating temperature range
-25 to +60 ℃
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
EN61439-1, EN61439-2; Railway EN51024-1
OPUS HE 48-10.0 R12U P
Power Out Max (kW) 10.0
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 42 - 59
Output Current Max (A) 208.5
Cooling Natural Convection
Max # Outputs
1
Module Positions
5
V1 Out Min (V)
42
V1 Out Nom (V)
48
V1 Out Max (V)
59
Efficiency Rating (%)
97
Operating Altitude (m)
2000
Operating temperature range
-25 to +60 ℃
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
EN/IEC 62368-1, EN 50124-1 Railway
OPUS HE 60-10.0 R12U P
Power Out Max (kW) 10
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 51 - 72
Output Current Max (A) 166.7
Cooling Natural Convection
Max # Outputs
1
Module Positions
5
V1 Out Min (V)
51
V1 Out Nom (V)
60
V1 Out Max (V)
72
Efficiency Rating (%)
97
Operating Altitude (m)
2000
Operating temperature range
-25 to +60 ℃
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
EN61439-1, EN61439-2; Railway EN51024-1
OPUS HE 110-10.0 R12U F
Power Out Max (kW) 10.0
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 90 - 150
Output Current Max (A) 92.5
Cooling Natural Convection
Max # Outputs
1
Module Positions
5
V1 Out Min (V)
90
V1 Out Nom (V)
110
V1 Out Max (V)
150
Efficiency Rating (%)
97
Operating Altitude (m)
2000
Operating temperature range
-25 to +60 ℃
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
EN/IEC 62368-1, EN 50124-1 Railway
OPUS HE 125-10.0 R12U F
Power Out Max (kW) 10
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 100 - 160
Output Current Max (A) 83.3
Cooling Natural Convection
Max # Outputs
1
Module Positions
5
V1 Out Min (V)
100
V1 Out Nom (V)
125
V1 Out Max (V)
160
Efficiency Rating (%)
97
Operating Altitude (m)
2000
Operating temperature range
-25 to +60 ℃
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
EN61439-1, EN61439-2; Railway EN51024-1
OPUS HE 220-10.0 R12U F
Power Out Max (kW) 10.0
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 178 - 280
Output Current Max (A) 46.3
Cooling Natural Convection
Max # Outputs
1
Module Positions
5
V1 Out Min (V)
178
V1 Out Nom (V)
220
V1 Out Max (V)
280
Efficiency Rating (%)
97
Operating Altitude (m)
2000
Operating temperature range
-25 to +60 ℃
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
EN61439-1, EN61439-2; Railway EN51024-1

The OPUS HE system consists of MHE rectifiers, VIDI+ controllers, connections for mains and battery, and load distribution MCB. Offered in a 19″ 12U rack, the system delivers a maximum 10 kW output power at 48, 60, 110, 125 and 200 VDC, and 7.5 kW at 24 VDC outputs.

The 19″ 12U rack system provides slots for a maximum of five (5) MHE rectifier modules. Load distribution configuration of MCB quantity and current ratings can be configured at time of order. Wall mounting, IP21 cover kit, temperature sensor and BLVD are available as options.

OPUS HE R7U SLAVE RACK

  • Supports up to five (5) MHE rectifiers
  • Mechanical housing only – no wiring
  • 19″ 7U Rack-mountable
  • Compatible with OPUS HE 7U systems
OPUS HE Accessories

OPUS Battery Fuse Box
• Wall Mountable Fuse Box for Battery Installations
• Switch Fuse Protection
• Configurable Fuse Link
• Up to 125A

Datasheet – OPUS Battery Fuse Box

OPUS Battery Cabinet For Front Terminal Batteries
• 4 Battery shelves 320 x 530 x 595 mm
• User terminals 35 mm (8 pcs)
• Cable entry from top, neoprene cable glands (optional bottom cable entry)
• Adjustable legs

Datasheet – OPUS Battery Cabinet For Front Terminal Batteries

OPUS IC Battery Cabinets with Switch Fuse Protection
• Battery shelves for up to 4 x 48V/190Ah batteries
• Switch fuse protected battery strings (4 x 125A NH00 – fuse monitoring)
• Cable entry from top
• Ventilation output on the top
• Adjustable legs
• Strong welded structure
• Top lifting eyes

Datasheet – OPUS IC Battery Cabinets with Switch Fuse Protection