OPUS HE BULK RACK

OPUS HE bulk rack is intended for local cabinet system builders. Local builder can use standard building block from Enedo and install it to right type of cabinet with batteries. Bulk rack includes readymade cable connections and parameter settings, which reduces significantly the design and manufacturing costs needed in local system builder side. OPUS HE bulk rack is ideal solution for local partner to increase the flexibility and value provided for local end customers

The new OPUS HE series provides free air convection cooling, N+1 redundancy and is the ideal backup power solution for critical infrastructure applications such as transmission and distribution substations, process industries, railway signaling and substations, and telecommunications.

Key features

  • Efficiency up to 97%
  • Natural convection cooled – fan free
  • Standard output voltages: 24, 48, 60, 110, 125 and 220 VDC
  • 2-12 kW power (24V 1.5kW-9kW), 1-6 rectifiers per rack
  • Master-Slave connection up to 24kW per cabinet or up to 64kW in multi cabinet
  • Air flow plate for optimized cooling
  • Air flow plate guides cooling air to backside of the cabinet and creates chimney effect
  • Rectifier input and output breakers included to the rack
  • Bulk output, battery terminals and battery shunt included
  • EMC ratings:
    Rack: EN61439-1, EN61439-2
    Rectifiers: EN 61000-6-1 / -2 / -3 / -4 / -5
    EN50121-4 Rail, ETSI EN 300386 (48/60V)
  • Safety ratings:
    Rack: EN61439-1, EN61439-2
    Rectifiers: EN 62368-1, EN 50124-1 rail

Applications

  • Critical infrastructure
  • Power transmission substations
  • Power distribution substations
  • Railway signaling and substations
  • Process industries
  • Telecommunications
Model number
Power Out Max (kW)
Input Voltage (VAC)
Output Voltage Range (VDC)
Output Current Max (A)
Cooling
OPUS HE 24-9.0 BULK R9U F
Power Out Max (kW) 9.0
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 21 - 33
Output Current Max (A) 375
Cooling Natural Convection
Module Positions
6
V1 Out Min (V)
21
V1 Out Nom (V)
24
V1 Out Max (V)
33
Output Current Max (A)
375
Efficiency Rating (%)
96
Operating Altitude (m)
3000
Operating temperature range
-25 to +60 ℃, see de-rating
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
Rack: EN61439-1, EN61439-2
OPUS HE 24-9.0 BULK SLAVE R9U F
Power Out Max (kW) 48.0
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 21 - 33
Output Current Max (A) 2000
Cooling Natural Convection
Module Positions
6 / 32
V1 Out Min (V)
21
V1 Out Nom (V)
24
V1 Out Max (V)
33
Output Current Max (A)
2000
Efficiency Rating (%)
96
Operating Altitude (m)
3000
Operating temperature range
-25 to +60 ℃, see de-rating
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
Rack: EN61439-1, EN61439-2
OPUS HE 48-12.0 BULK R9U F
Power Out Max (kW) 12.0
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 42 - 59
Output Current Max (A) 250
Cooling Natural Convection
Module Positions
6
V1 Out Min (V)
42
V1 Out Nom (V)
48
V1 Out Max (V)
59
Output Current Max (A)
250
Efficiency Rating (%)
97
Operating Altitude (m)
3000
Operating temperature range
-25 to +60 ℃, see de-rating
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
Rack: EN61439-1, EN61439-2
OPUS HE 48-12.0 BULK SLAVE R9U F
Power Out Max (kW) 64.0
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 42 - 59
Output Current Max (A) 1334
Cooling Natural Convection
Module Positions
6 / 32
V1 Out Min (V)
42
V1 Out Nom (V)
48
V1 Out Max (V)
59
Output Current Max (A)
1334
Efficiency Rating (%)
97
Operating Altitude (m)
3000
Operating temperature range
-25 to +60 ℃, see de-rating
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
Rack: EN61439-1, EN61439-2
OPUS HE 60-12.0 BULK R9U F
Power Out Max (kW) 12.0
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 51 - 72
Output Current Max (A) 200
Cooling Natural Convection
Module Positions
6
V1 Out Min (V)
51
V1 Out Nom (V)
60
V1 Out Max (V)
72
Output Current Max (A)
200
Efficiency Rating (%)
97
Operating Altitude (m)
3000
Operating temperature range
-25 to +60 ℃, see de-rating
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
Rack: EN61439-1, EN61439-2
OPUS HE 60-12.0 BULK SLAVE R9U F
Power Out Max (kW) 64.0
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 51 - 72
Output Current Max (A) 1067
Cooling Natural Convection
Module Positions
6 / 32
V1 Out Min (V)
51
V1 Out Nom (V)
60
V1 Out Max (V)
72
Output Current Max (A)
1067
Efficiency Rating (%)
97
Operating Altitude (m)
3000
Operating temperature range
-25 to +60 ℃, see de-rating
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
Rack: EN61439-1, EN61439-2
OPUS HE 110-12.0 BULK R9U F
Power Out Max (kW) 12.0
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 90 - 150
Output Current Max (A) 111
Cooling Natural Convection
Module Positions
6
V1 Out Min (V)
90
V1 Out Nom (V)
110
V1 Out Max (V)
150
Output Current Max (A)
111
Efficiency Rating (%)
96
Operating Altitude (m)
3000
Operating temperature range
-25 to +60 ℃, see de-rating
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
Rack: EN61439-1, EN61439-2
OPUS HE 110-12.0 BULK SLAVE R9U F
Power Out Max (kW) 64.0
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 90 - 150
Output Current Max (A) 592
Cooling Natural Convection
Module Positions
6 / 32
V1 Out Min (V)
90
V1 Out Nom (V)
110
V1 Out Max (V)
150
Output Current Max (A)
592
Efficiency Rating (%)
96
Operating Altitude (m)
3000
Operating temperature range
-25 to +60 ℃, see de-rating
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
Rack: EN61439-1, EN61439-2
OPUS HE 125-12.0 BULK R9U F
Power Out Max (kW) 12.0
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 100 - 160
Output Current Max (A) 100
Cooling Natural Convection
Module Positions
6
V1 Out Min (V)
100
V1 Out Nom (V)
125
V1 Out Max (V)
160
Output Current Max (A)
100
Efficiency Rating (%)
96
Operating Altitude (m)
3000
Operating temperature range
-25 to +60 ℃, see de-rating
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
Rack: EN61439-1, EN61439-2
OPUS HE 125-12.0 BULK SLAVE R9U F
Power Out Max (kW) 64.0
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 100 - 160
Output Current Max (A) 533
Cooling Natural Convection
Module Positions
6 / 32
V1 Out Min (V)
100
V1 Out Nom (V)
125
V1 Out Max (V)
160
Output Current Max (A)
533
Efficiency Rating (%)
96
Operating Altitude (m)
3000
Operating temperature range
-25 to +60 ℃, see de-rating
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
Rack: EN61439-1, EN61439-2
OPUS HE 220-12.0 BULK R9U F
Power Out Max (kW) 12.0
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 178 - 280
Output Current Max (A) 55.5
Cooling Natural Convection
Module Positions
6
V1 Out Min (V)
178
V1 Out Nom (V)
220
V1 Out Max (V)
280
Output Current Max (A)
55.5
Efficiency Rating (%)
96
Operating Altitude (m)
3000
Operating temperature range
-25 to +60 ℃, see de-rating
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
Rack: EN61439-1, EN61439-2
OPUS HE 220-12.0 BULK SLAVE R9U F
Power Out Max (kW) 64.0
Input Voltage (VAC) 85 - 300
Output Voltage Range (VDC) 178 - 280
Output Current Max (A) 296
Cooling Natural Convection
Module Positions
6 / 32
V1 Out Min (V)
178
V1 Out Nom (V)
220
V1 Out Max (V)
280
Output Current Max (A)
296
Efficiency Rating (%)
96
Operating Altitude (m)
3000
Operating temperature range
-25 to +60 ℃, see de-rating
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
Rack: EN61439-1, EN61439-2

This new high efficiency power system consists of Enedo’s MHE rectifiers, VIDI+ controllers, connections for mains and battery connection with shunt resistor  and bulk screw terminal for external load distribution. Available as a 23″ 9U rack-mountable package or side wall mountable. The system delivers a maximum 12 kW output power at 48, 60, 110, 125 and 220 VDC, and 9 kW at 24 VDC output. The base system supports up to six (6) MHE series high efficiency rectifiers, but may be expanded by using the Slave Rack in a master-slave configuration, increasing the power capability to 64 kW in multi cabinet configuration.

OPUS HE R7U SLAVE RACK

  • Supports up to five (5) MHE rectifiers
  • Mechanical housing only – no wiring
  • 19″ 7U Rack-mountable
  • Compatible with OPUS HE 7U systems
OPUS HE Accessories

OPUS Battery Fuse Box
• Wall Mountable Fuse Box for Battery Installations
• Switch Fuse Protection
• Configurable Fuse Link
• Up to 125A

Datasheet – OPUS Battery Fuse Box

OPUS Battery Cabinet For Front Terminal Batteries
• 4 Battery shelves 320 x 530 x 595 mm
• User terminals 35 mm (8 pcs)
• Cable entry from top, neoprene cable glands (optional bottom cable entry)
• Adjustable legs

Datasheet – OPUS Battery Cabinet For Front Terminal Batteries

OPUS IC Battery Cabinets with Switch Fuse Protection
• Battery shelves for up to 4 x 48V/190Ah batteries
• Switch fuse protected battery strings (4 x 125A NH00 – fuse monitoring)
• Cable entry from top
• Ventilation output on the top
• Adjustable legs
• Strong welded structure
• Top lifting eyes

Datasheet – OPUS IC Battery Cabinets with Switch Fuse Protection