Skip to content

OPUS C Modular Wall-Mount DC Power System

The OPUS C Wall-mount DC Power systems are natural convection cooled, modular wall-mounted charging rectifier systems for industrial market applications. These systems can be combined with batteries to provide uninterrupted DC power for critical applications.

Key features

  • Modular wall-mount DC power system
  • N+1 redundancy
  • Natural convection cooling – low noise operation
  • Easy installation
  • Standard output variants include 24, 48, 60, 110 & 220 VDC
    • Maximum output power 9.6 kW:
    • – 6.6 kW for 24 VDC models
  • Battery connection: 1 string with full current:
    • Switch fuse protection
  • Safety: IEC/EN 60950-1

Applications

  • Industrial systems
  • Process control
  • Telecommunications
Model number
Power Out Max (kW)
Power Out Max (W)
Input Voltage (VAC)
Output Voltage Range (VDC)
Output Current Max (A)
Cooling
OPUS C 24-6.6 CS0864 F
Power Out Max (kW) 6.6
Power Out Max (W)
Input Voltage (VAC) 180 - 275
Output Voltage Range (VDC) 21 - 31
Output Current Max (A) 275
Cooling Natural Convection
Module Positions
6
V1 Out Min (V)
21
V1 Out Nom (V)
24
V1 Out Max (V)
31
Output Current Min (A)
240
Operating Altitude (m)
2000
Operating temperature range
-20°C to +45°C
IP Rating
IP20 / IP21
Safety
IEC/EN 60950-1, CE Mark
OPUS C 110-9.6 CS0864 F
Power Out Max (kW) 9.6
Power Out Max (W)
Input Voltage (VAC) 180 - 275
Output Voltage Range (VDC) 97 - 132
Output Current Max (A) 87
Cooling Natural Convection
Module Positions
6
V1 Out Min (V)
79
V1 Out Nom (V)
110
V1 Out Max (V)
132
Output Current Min (A)
78
Operating Altitude (m)
2000
Operating temperature range
-20°C to +45°C
IP Rating
IP20 / IP21
Safety
IEC/EN 60950-1, CE Mark
OPUS C 220-9.6 CS0864 F
Power Out Max (kW) 9.6
Power Out Max (W)
Input Voltage (VAC) 180 - 275
Output Voltage Range (VDC) 189 - 265
Output Current Max (A) 43
Cooling Natural Convection
Module Positions
6
V1 Out Min (V)
189
V1 Out Nom (V)
220
V1 Out Max (V)
265
Output Current Min (A)
39
Operating Altitude (m)
2000
Operating temperature range
-20°C to +45°C
IP Rating
IP20 / IP21
Safety
IEC/EN 60950-1, CE Mark
OPUS C 48-9.6 CS0864 F
Power Out Max (kW) 9.6
Power Out Max (W)
Input Voltage (VAC) 180 - 275
Output Voltage Range (VDC) 42 - 58
Output Current Max (A) 197
Cooling Natural Convection
Module Positions
6
V1 Out Min (V)
42
V1 Out Nom (V)
48
V1 Out Max (V)
58
Output Current Min (A)
177
Operating Altitude (m)
2000
Operating temperature range
-20°C to +45°C
IP Rating
IP20 / IP21
Safety
IEC/EN 60950-1, CE Mark
OPUS C 60-9.6 CS0864 F
Power Out Max (kW) 9.6
Power Out Max (W)
Input Voltage (VAC) 180 - 275
Output Voltage Range (VDC) 51 - 72
Output Current Max (A) 161
Cooling Natural Convection
Module Positions
6
V1 Out Min (V)
51
V1 Out Nom (V)
60
V1 Out Max (V)
72
Output Current Min (A)
141
Operating Altitude (m)
2000
Operating temperature range
-20°C to +45°C
IP Rating
IP20 / IP21
Safety
IEC/EN 60950-1, CE Mark

OPUS C Wall-mount power systems are an industrial grade solution family that delivers uninterrupted power for whole voltage ranges from 24V to 220VDC. With highly efficient, convection-cooled rectifiers, a state-of-the-art controller, and a highly modular mechanical structure, the OPUS C Series can be easily configured to meet a multitude of telecom and industrial applications.

OPUS Wall-mount systems come in an IP20 / IP21 enclosure and consist of the MRC rectifiers (up to 6 modules), VIDI+ I/O controller, switch fuse protection for the battery and MCB protection for the mains. For lead connections there are both bulk screw terminal outputs and a couple of configurable MCBs.

OPUS Battery Fuse Box
• Wall Mountable Fuse Box for Battery Installations
• Switch Fuse Protection
• Configurable Fuse Link
• Up to 125A

Datasheet – OPUS Battery Fuse Box

OPUS Battery Cabinet For Front Terminal Batteries
• 4 Battery shelves 320 x 530 x 595 mm
• User terminals 35 mm (8 pcs)
• Cable entry from top, neoprene cable glands (optional bottom cable entry)
• Adjustable legs

Datasheet – OPUS Battery Cabinet For Front Terminal Batteries

OPUS IC Battery Cabinets with Switch Fuse Protection
• Battery shelves for up to 4 x 48V/190Ah batteries
• Switch fuse protected battery strings (4 x 125A NH00 – fuse monitoring)
• Cable entry from top
• Ventilation output on the top
• Adjustable legs
• Strong welded structure
• Top lifting eyes

Datasheet – OPUS IC Battery Cabinets with Switch Fuse Protection