OPUS MVPS 12U AC & DC Power System

OPUS MVPS Multi Voltage Power Systems offer a robust, free air convection cooled, N+1 redundant backup power solution for critical infrastructure applications such as transmission and distribution substations, process industries, railway signaling and substations, and telecommunications.

Key features

  • Efficiency off-line AC loads 99%, DC loads up to 97%, inverter efficiency 90%
  • Natural convection cooled or temp.compensated fan in inverters
  • Output DC voltages: 24, 48, 60, 110, 125 and 220 VDC
  • Output AC voltages: 200-240VAC
  • Max DC power 4 kW, max AC power 3.6kVA/3.6kW
  • N+1 redundancy
  • AC and DC Load distribution MCBs
  • Battery connection: MCB or terminal for external battery fuse
  • Options: Temperature sensor, wall mounting & IP21 cover kit
  • EMC ratings:
    Rack: EN61439-1, EN61439-2
    Modules: EN 61000-6-1 / -2 / -3 / -4 / (-5)
  • Safety ratings:
    Rack: EN61439-1, EN61439-2
    Modules: IEC 62368-1

Applications

  • Critical infrastructure
  • Power transmission substations
  • Power distribution substations
  • Railway signaling and substations
  • Process industries
  • Telecommunications
Model number
Power Out Max (kW)
Input Voltage (VAC)
V1 Out Nom (V)
V2 Out (V)
Cooling
OPUS MVPS 24-3.0 230-3.6 R12U F
Power Out Max (kW) DC 3kW & AC 3.6kVA
Input Voltage (VAC) 85 - 300
V1 Out Nom (V) 21-33VDC 125A
V2 Out (V) 200-240VAC 15A
Cooling Natural Convection
Max # Outputs
2
Module Positions
2+3
Efficiency Rating (%)
90% - 99%
Operating Altitude (m)
2000
Operating temperature range
-25/0 ℃ to +40/60 ℃
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
EN61439-1, EN61439-2
Warranty Years
2/5
OPUS MVPS 48-4.0 230-3.6 R12U F
Power Out Max (kW) DC 4kW & AC 3.6kVA
Input Voltage (VAC) 85 - 300
V1 Out Nom (V) 42-59VDC 83.3A
V2 Out (V) 200-240VAC 15A
Cooling Natural Convection
Max # Outputs
2
Module Positions
2+3
Efficiency Rating (%)
90% - 99%
Operating Altitude (m)
2000
Operating temperature range
-25/0 ℃ to +40/60 ℃
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
EN61439-1, EN61439-2
Warranty Years
2/5
OPUS MVPS 60-4.0 230-3.6 R12U F
Power Out Max (kW) DC 4kW & AC 3.6kVA
Input Voltage (VAC) 85 - 300
V1 Out Nom (V) 51-72VDC 66.7A
V2 Out (V) 200-240VAC 15A
Cooling Natural Convection
Max # Outputs
2
Module Positions
2+3
Efficiency Rating (%)
90% - 99%
Operating Altitude (m)
2000
Operating temperature range
-25/0 ℃ to +40/60 ℃
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
EN61439-1, EN61439-2
Warranty Years
2/5
OPUS MVPS 110-4.0 230-3.6 R12U F
Power Out Max (kW) DC 4kW & AC 3.6kVA
Input Voltage (VAC) 85 - 300
V1 Out Nom (V) 90-150VDC 37A
V2 Out (V) 200-240VAC 15A
Cooling Natural Convection
Max # Outputs
2
Module Positions
2+3
Efficiency Rating (%)
90% - 99%
Operating Altitude (m)
2000
Operating temperature range
-25/0 ℃ to +40/60 ℃
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
EN61439-1, EN61439-2
Warranty Years
2/5
OPUS MVPS 125-4.0 230-3.6 R12U F
Power Out Max (kW) DC 4kW & AC 3.6kVA
Input Voltage (VAC) 85 - 300
V1 Out Nom (V) 100-160VDC 33.3A
V2 Out (V) 200-240VAC 15A
Cooling Natural Convection
Max # Outputs
2
Module Positions
2+3
Efficiency Rating (%)
90% - 99%
Operating Altitude (m)
2000
Operating temperature range
-25/0 ℃ to +40/60 ℃
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
EN61439-1, EN61439-2
Warranty Years
2/5
OPUS MVPS 220-4.0 230-3.6 R12U F
Power Out Max (kW) DC 4kW & AC 3.6kVA
Input Voltage (VAC) 85 - 300
V1 Out Nom (V) 178-280VDC 18.5A
V2 Out (V) 200-240VAC 15A
Cooling Natural Convection
Max # Outputs
2
Module Positions
2+3
Efficiency Rating (%)
90% - 99%
Operating Altitude (m)
2000
Operating temperature range
-25/0 ℃ to +40/60 ℃
IP Rating
IP20
Control & Monitoring
VIDI+ Controller
Safety
EN61439-1, EN61439-2
Warranty Years
2/5

The OPUS MVPS Multi Voltage Power System consists of MHE rectifiers, DAC inverters, BPU bypass units, VIDI+ controllers, connections for mains and battery, and load distribution MCB. Offered in a 19″ 12U rack, the system delivers a maximum 4 kW DC power 24-220VDC and 3.6kVA AC power 200-240VAC.

The 19″ 12U rack system provides slots for a maximum 2 MHE rectifier modules and 3 inverter modules or 2 rectifiers, 2 inverters and bypass unit. Load distribution configuration of MCB quantity and current ratings can be configured at time of order. Wall mounting, IP21 cover kit, and temperature sensor are available as options.

OPUS HE R7U SLAVE RACK

  • Supports up to five (5) MHE rectifiers
  • Mechanical housing only – no wiring
  • 19″ 7U Rack-mountable
  • Compatible with OPUS HE 7U systems
OPUS HE Accessories

OPUS Battery Fuse Box
• Wall Mountable Fuse Box for Battery Installations
• Switch Fuse Protection
• Configurable Fuse Link
• Up to 125A

Datasheet – OPUS Battery Fuse Box

OPUS Battery Cabinet For Front Terminal Batteries
• 4 Battery shelves 320 x 530 x 595 mm
• User terminals 35 mm (8 pcs)
• Cable entry from top, neoprene cable glands (optional bottom cable entry)
• Adjustable legs

Datasheet – OPUS Battery Cabinet For Front Terminal Batteries

OPUS IC Battery Cabinets with Switch Fuse Protection
• Battery shelves for up to 4 x 48V/190Ah batteries
• Switch fuse protected battery strings (4 x 125A NH00 – fuse monitoring)
• Cable entry from top
• Ventilation output on the top
• Adjustable legs
• Strong welded structure
• Top lifting eyes